Sprinklers in warehouses: why racking changes everything
A warehouse sprinkler system is designed against a specific storage height, storage arrangement and commodity class. Raising the racking, changing what is stored or adding racking under a roof-only design can leave the system unable to control a fire it was never designed for.
Most of what is written about sprinklers assumes an office. Warehouses are a different problem, and the difference is not size. It is that the fire is inside the racking, not on the floor, and everything about the design follows from that.
The design was made once, against three things
A warehouse sprinkler system under BS EN 12845 is designed against a hazard classification, and that classification is set by three inputs:
- What is stored, the commodity class. Cardboard and paper behave very differently from plastics, aerosols, foam and packaged flammables.
- How high it is stored. Storage height is a direct input, not a detail.
- How it is arranged: open floor, block stacked, palletised racking, and how the aisles run.
Those three fixed the design density, the assumed area of operation and the water supply duration on the day the system was designed. They are then almost never revisited, while the business changes all three.
The three changes that quietly break a design
Racking gets taller
The cheapest way to add capacity is upwards, and nothing about it looks like a fire safety decision. Raise the top beam by a metre and the storage height changes, which changes the classification, which changes the density the system needed to deliver.
The system does not become dangerous overnight, and it will still operate. It may simply no longer be able to control a fire in the load it now has to reach.
The commodity changes
A third-party logistics operator taking on a new contract can move from paper goods to plastic-packaged consumer goods in a fortnight. The building is identical. The fire is not: plastics burn hotter, faster and with far more heat release, and the water needed to control them is substantially greater.
Racking is added where there was none
A section designed as open floor, with roof-level sprinklers spaced for open floor, gets racked out. Now there is a load between the sprinkler and the fire, and the water that used to reach the floor lands on the top of a pallet.
Roof-level, in-rack and ESFR
Three ways of getting water to a fire in a rack, and warehouses use all of them.
Standard roof-level sprinklers. Adequate up to certain storage heights and commodity classes. Past that, the plume from a rack fire is strong enough that water from the roof does not get down through it.
In-rack sprinklers. Heads and pipework mounted inside the racking, at one or more tiers, attacking the fire where it is. They work well and they are exposed: forklift damage to in-rack pipework is one of the most common causes of accidental discharge in warehousing. Guards help. Driver awareness helps more.
ESFR. Early Suppression Fast Response heads at roof level: large orifice, fast-response element, designed to drive enough water through the plume to suppress the fire rather than merely control it. Where the conditions allow it, ESFR removes the need for in-rack sprinklers entirely, which is why it dominates modern distribution buildings.
Those conditions are strict. Roof height and profile, obstructions such as ductwork and lighting, aisle widths and storage arrangement all constrain it, and an ESFR design is invalidated more easily than people expect by services installed under the roof afterwards.
What obstructs a warehouse system
The most common real-world faults we find in warehouses are not mechanical. They are things put in the way.
- Stock stacked too close to the heads. There is a required clearance below a sprinkler, and a pallet stacked into it does not just block that head, it disrupts the spray pattern for the ones around it.
- Services installed under the sprinklers. New lighting, ductwork, cable tray and conveyor lines fitted after commissioning, sitting between the head and the floor.
- Mezzanines added without sprinklers underneath. A mezzanine creates a new ceiling, and the space under it is now unprotected.
- Racking changed without the layout being reviewed. Aisles moved, so the head layout no longer relates to the aisles.
None of these appears on a service report as a fault, because none of them is a fault in the system. They are faults in the relationship between the system and the building, and they need somebody looking at both.
What to do about it
The annual service proves the system works as designed. It does not prove the design still fits the building, and no service regime will tell you that. Those are different questions and they need asking separately.
A practical rule for anyone running a warehouse:
- If storage height, commodity or racking layout has changed since the system was designed, have the design reviewed. Not the system serviced. Reviewed.
- Tell your insurer. Commodity class is priced. Finding out at a claim that the stored goods were outside the design is the worst possible time.
- Walk the floor once a year looking upwards, at clearances, at obstructions and at anything installed under the sprinklers since last time.
The maintenance side of it, the intervals and what each visit covers, is BS EN 12845 in plain English and sprinkler servicing intervals.
Most of the buildings we look after are warehouses and distribution units, and the survey is free. If any of the three changes above has happened on your site, that is the conversation worth having, and it is sprinkler servicing or a design review under design and installation depending on what it turns up.
This work, on our sites
Questions we get asked
We raised our racking by a metre. Does that matter?
Very possibly. Storage height is a direct input to the hazard classification under BS EN 12845, and the design density and the water supply duration follow from it. Raising racking is one of the few building changes that can move a compliant system to an inadequate one without touching a single sprinkler head, and it is not something the annual service will flag.
What is ESFR, and do we need it?
Early Suppression Fast Response: a large-orifice, fast-acting roof-level head designed to put enough water through the fire plume to suppress a rack fire from above, rather than merely control it. Where it can be used it removes the need for in-rack sprinklers, which is why it is popular. It has strict conditions on roof height, obstructions and storage arrangement, and it is a design decision rather than a preference.
Why do some warehouses have sprinklers inside the racking?
Because at certain storage heights and commodity classes, roof-level sprinklers cannot get water down through the load to the seat of the fire. In-rack heads sit within the racking and attack it directly. They work, and they are vulnerable: forklift damage to in-rack pipework is one of the most common causes of accidental discharge in a warehouse.
Does changing what we store need anyone told?
It needs your fire risk assessment reviewed and, in most cases, your insurer told. Commodity class is a design input, and plastics, aerosols, foam and packaged flammable goods behave very differently from cardboard and paper. Moving into a higher class without a design review is one of the most consequential things a business can do to its own fire protection.
Where this comes from
- BS EN 12845Fixed firefighting systems. Automatic sprinkler systems. Design, installation and maintenance
The standard commercial and industrial sprinkler systems are designed, installed and maintained to. It sets the weekly, monthly, quarterly and annual routines.
BSI
- LPC RulesLPC Rules for Automatic Sprinkler Installations, incorporating BS EN 12845
The insurer-facing ruleset that sits alongside BS EN 12845. Part 1 is the standard itself; the technical bulletins in Part 2 are what an insurer means by property protection.
Fire Protection Association
British Standards are copyright documents and most are bought rather than read free. We hold the ones we work to. If you need to know what one of them says about your building, ask us rather than buying it.