Four types of sprinkler system, and how to tell them apart.

Wet pipe, dry pipe, pre-action and deluge. They differ in one thing: what is in the pipe before the fire. That single difference decides how fast water arrives, where each can be used, and what a service visit has to include.

The four systems compared

Wet pipe

The great majority of UK buildings

In the pipe
Water, permanently
Water arrives
Fastest

The pipework is full of water at all times. A head opens and water comes out of that head immediately. There is nothing else to happen.

Used in. Anywhere that never drops below freezing: offices, shops, warehouses, flats.

Watch for. It cannot be used anywhere that freezes. A wet system in an unheated loading bay or an external canopy will split, and the first anyone knows is the thaw.

Dry pipe

Cold stores, loading bays, canopies

In the pipe
Pressurised air
Water arrives
Delayed

The pipework holds compressed air. A head opens, the air escapes, the pressure drop trips a dry alarm valve at the control set and water then travels up the pipe to the open head.

Used in. Unheated spaces, and only where the temperature genuinely justifies it.

Watch for. There is a delay between the head opening and water arriving, so the standard limits how much pipe volume one valve may serve. It is also the system most damaged by trapped water, which is why the pipework has to be laid to fall and drained properly.

Pre-action

Data centres, archives, galleries

In the pipe
Air, plus a separate detector
Water arrives
Delayed, deliberately

Two things have to happen. A fire detection system has to detect, AND a sprinkler head has to open. Only then does water enter the pipework. A single event does nothing.

Used in. Rooms where an accidental discharge would cost more than the fire.

Watch for. It is two systems that both have to be maintained, and the interlock between them is the part that gets forgotten. A pre-action system with a detection head out of service is not a pre-action system.

Deluge

Process risks, transformers, flammable storage

In the pipe
Empty, with open heads
Water arrives
Whole zone at once

The heads have no heat element at all. They are simply open nozzles. A detection system opens a deluge valve and every head in the zone discharges together.

Used in. High hazard, where a fire will spread faster than head-by-head operation can control it.

Watch for. Water volumes are very large and the drainage has to be designed for it. This is a process engineering decision, not a building services one.

How a head actually triggers, and why only the heads over the fire open, is in the guide on how a sprinkler system works.

What makes a commercial fire sprinkler system different

The four types above appear in both, but a commercial system and a residential one are designed to different standards for different purposes, and they are maintained differently as a result.

BS EN 12845

Commercial and industrial

A property protection standard. The building is classified by hazard, the design density and area of operation follow from that, and the water supply has to be proved for a required flow and duration. Warehouses, retail, offices, basement car parks and plant rooms.

BS 9251

Residential and domestic

A life safety standard. Get the occupants out, using a smaller supply often taken off the domestic main, with concealed heads that do not look industrial. Blocks of flats, student accommodation, care homes.

A single building can hold both: flats to BS 9251 above a car park to BS EN 12845, on separate designs and separate service regimes. Where that line falls is in our guide to residential sprinklers.

Five heads you will see

The head is chosen for the ceiling and the risk, not for looks, and the wrong one in the wrong place is a defect rather than a preference.

  1. 01

    Pendent

    Hangs down below the ceiling. The default in a suspended ceiling, and the one most people picture.

  2. 02

    Upright

    Sits above the pipe, spraying up into a deflector. Used on exposed pipework under a deck or in a roof void, where a pendent would collect dust and damage.

  3. 03

    Sidewall

    Fires horizontally from a wall. Used in corridors and small rooms where running pipework across the ceiling is not worth it.

  4. 04

    Concealed

    A pendent behind a flat cover plate that drops away with heat. Chosen where the ceiling matters: receptions, hotels, flats. The cover plate is part of the listed assembly and must not be painted.

  5. 05

    ESFR

    Early Suppression Fast Response. A large-orifice, fast-response roof-level head for warehousing, designed to drive water through a rack fire plume and suppress it rather than control it.

Three sprinkler control valve sets installed on a plant room wall
Three sprinkler control valve sets installed on a plant room wall
Sprinkler drops from a concrete soffit
Sprinkler drops from a concrete soffit
In-rack sprinkler pipework in a warehouse
In-rack sprinkler pipework in a warehouse

What the bulb colour means

The liquid in the glass bulb is colour coded to its operating temperature. It is the quickest way to tell whether the head above you is the right one for the room it is in.

  • 57°C Orange
  • 68°C Red
  • 79°C Yellow
  • 93°C Green
  • 141°C Blue
  • 182°C Mauve

Red and yellow cover most ordinary occupancies. A higher rating goes near roof lights, kitchens, plant rooms and anywhere the ambient temperature would otherwise trip a standard head.

Questions about system types

How do I tell which type of system my building has?

Look at the control valve set rather than the ceiling. A wet system has one main gauge above and below the alarm valve and no compressor. A dry system has an air compressor and a second, lower pressure reading on the air side. A pre-action set has a detection panel wired into it. If in doubt, the commissioning certificate names the system type.

What does the colour of the glass bulb mean?

It is the operating temperature of that head. Orange is 57°C, red 68°C, yellow 79°C, green 93°C, blue 141°C and mauve 182°C. Red and yellow cover most ordinary occupancies. A higher rating is used near heat sources such as roof lights, kitchens and plant so the head does not operate on ambient heat.

Can a concealed sprinkler head be painted?

No. The cover plate is a listed part of the assembly and it is designed to drop away at a set temperature. Painting it changes that, and a painted cover plate is a defect on any inspection. The same applies to the head itself: a painted sprinkler head must be replaced, not cleaned.

Is a pre-action system safer than a wet one?

Not for fire. It is safer for the contents against an accidental discharge, which is why data centres and archives use it. For fire performance a wet pipe system is the fastest of the four, because there is nothing between the head opening and water arriving.

Do the different types need different servicing?

The intervals are the same under BS EN 12845, but the work is not. A dry or pre-action set adds air pressure checks, compressor checks and a trip test of the dry valve, and a pre-action system adds proving the interlock with the detection system. A quotation that prices a dry system as though it were wet has missed several items.

Not sure which you have? The commissioning certificate names it, and if nobody can find one an engineer can tell from the valve set in about a minute.

Where the figures on this page come from

Which type of system a building needs, and what it has to achieve once installed, is set by these.

British Standards are copyright documents and most are bought rather than read free. We hold the ones we work to. If you need to know what one of them says about your building, ask us rather than buying it.

Tell us the building. We will tell you what it is due.

No survey fee to find out where you stand. Describe the site and we will tell you which intervals apply and what the visit involves.

Based
37 Dickens Drive, Kettering, NN16 9EG
Covering
Kettering · Corby · Wellingborough · Northampton · Rushden · Daventry · Market Harborough · Bedford and England, from our base in Kettering
Office hours
Monday to Friday, 7am to 5pm. Emergency line any hour.

What do you need?
    Who do we come back to?

    If it is urgent, ring rather than write. We are on the phone Monday to Friday, 7am to 5pm, and outside those hours the same number reaches the emergency line.

    Or send it straight to us

    Or just ring 07927 555475 and talk it through. Mon to Fri, 7am to 5pm. Emergencies any hour.