Sprinklers

How far apart do fire sprinklers need to be?

Under BS EN 12845, ceiling sprinklers in the UK can be up to 4.6 m apart in a light hazard building, 4.0 m in ordinary hazard and 3.7 m in high hazard, and never closer than 2 m. Each head covers at most 21, 12 or 9 square metres, explains Sentry Sprinkler Protection.

BS EN 12845LPC Rules 6 November 2026 4 min read by Sentry Sprinkler Protection

Book a free survey or ring 07927 555475

High level sprinkler main under an exposed metal deck
High level sprinkler main under an exposed metal deck. One of ours.

Fire sprinklers in the UK can be up to 4.6 m apart, but how far depends on what the building is used for. BS EN 12845, the standard commercial systems are designed to, sorts every space into a hazard class, and each class has its own maximum spacing and maximum area per head. The rules also set a minimum distance between heads and limits from walls and ceilings. Sentry Sprinkler Protection checks this layout on every survey, because a change of use inside a building can leave the heads too far apart for what is now stored beneath them.

The spacing table

For ordinary ceiling sprinklers (everything except sidewall heads), BS EN 12845 Table 19 sets:

Hazard classTypical buildingsMax area per headMax distance apart
Light hazard (LH)Low fire load areas split into rooms of no more than 126 m², such as some offices and schools21 m² (about 226 sq ft)4.6 m
Ordinary hazard (OH)Most commercial buildings: offices, hotels, hospitals, schools, car parks, shops and shopping centres, most factories12 m² (about 129 sq ft)4.0 m, or 4.6 m along a staggered line
High hazard (HHP and HHS)High hazard processes and storage9 m² (about 97 sq ft)3.7 m

The distances are measured between heads along a range pipe and between the range pipes themselves, and both limits apply at once. Heads 4.0 m apart in both directions cover 16 m², which is inside the light hazard limit but outside the ordinary hazard one, so an ordinary hazard layout has to bring the lines closer together.

“Per square foot” is how the question is usually typed, and the answer is the other way round: it is not so many heads per square foot, it is one head per so many square feet, between about 97 and 226 depending on the hazard class.

The minimum: 2 metres

Heads must not be closer than 2 m (clause 12.3). A head that is too close to its neighbour gets wet when the neighbour opens, the spray cools its bulb, and it may then fail to open when the fire reaches it. The standard allows closer spacing only where baffles or the building’s structure stop one head wetting the next, for intermediate heads inside storage racks, and around escalators and stairwells.

Distance from walls

The furthest a head can be from a wall or partition is the smallest of these (clause 12.4.1):

  • 2.0 m for a standard layout, or 2.3 m for a staggered one;
  • 1.5 m where the roof has open joists or exposed rafters;
  • 1.5 m from the open face of an open-sided building;
  • 1.5 m beside external walls that are combustible, or made of metal;
  • half the maximum spacing in the table for that hazard class.

Walls matter because a fire against a wall is a fire at the edge of the pattern, where fewer heads can reach it.

Distance below the ceiling

Heat rises and spreads under the ceiling first, so heads have to be close to it. Where possible the deflector sits 75 mm to 150 mm below the ceiling or roof, and never more than 0.3 m below a combustible ceiling or 0.45 m below a non-combustible one (clause 12.4.2). Beams, ducts and lights that interrupt the spray have their own rules on top of these.

Sidewall heads

Sidewall sprinklers, which throw water out from the wall rather than down from the ceiling, are spaced by Table 20: up to 4.6 m apart and 17 m² each in light hazard, and 3.4 m apart and 9 m² each in ordinary hazard (3.7 m where the ceiling has at least 120 minutes’ fire resistance). They are mostly used in corridors and small rooms.

Warehouses, racks and special heads

Storage changes everything. High-piled goods, in-rack sprinklers and ESFR heads have their own spacing rules, set by storage height and commodity rather than by this table, and the LPC Rules allow certain extended coverage heads to be spaced further apart than Table 19 where the manufacturer’s data supports it (TB222). Our guide to sprinklers in warehouses covers those cases.

Why heads per pipe size is the wrong question

You will find tables online that say how many heads a 25 mm or 32 mm pipe can feed. Those are pipe schedules from older pre-calculated designs. A system to BS EN 12845 is sized by hydraulic calculation: the pipe has to deliver the design density over the assumed area of operation for that hazard class, from the actual water supply. Two buildings with the same number of heads can need different pipe sizes. Our BS EN 12845 guide explains hazard classes and design density.

Checking your own layout

If a building has changed use, been refitted with new ceilings or partitions, or now stores goods higher than it used to, the spacing that was right when the system was installed may not be right now. A sprinkler service includes a review of the hazard against the installation, and where heads have to be added or moved, our sprinkler installation team designs the change to BS EN 12845.

This work, on our sites

Questions we get asked

Can fire sprinklers be closer than 2 metres apart?

Only in three cases BS EN 12845 allows: where baffles or the building structure stop one head wetting the next, for intermediate heads inside storage racks, and around escalators and stairwells. Otherwise the 2 m minimum stands, because a head that is soaked by its neighbour cools down and may not open when the fire reaches it.

How far from a wall can a sprinkler head be?

No more than 2.0 m with a standard layout, or 2.3 m with a staggered one, and no more than 1.5 m where the roof has open joists or exposed rafters, at the open face of an open-sided building, or beside external walls that are combustible or made of metal. In every case it must also be no more than half the maximum spacing for the hazard class.

How far below the ceiling should a sprinkler be?

Where possible, BS EN 12845 places the deflector between 75 mm and 150 mm below the ceiling or roof, except for ceiling, flush and recessed patterns. It must never be more than 0.3 m below a combustible ceiling or 0.45 m below a non-combustible one, because heat collects at the ceiling and a head too far below it opens late.

Where this comes from

British Standards are copyright documents and most are bought rather than read free. We hold the ones we work to. If you need to know what one of them says about your building, ask us rather than buying it.

Read on

Read next How many fire pumps does a sprinkler system need? A sprinkler system fed from a tank by one pump has a single water supply. Where the insurer, a high-rise building or a life safety design needs a more reliable supply, BS EN 12845 calls for two or more pumps, and normally no more than one of them may be electric, explains Sentry Sprinkler Protection.

When is your next visit due?

Pick the system and the month a contractor last came. You will see each routine, the date it falls due and anything that is already late.

Weekly checks are your own team's, logged on site. Our free weekly test log covers them on one page.

1 · The system

2 · The last contractor visit

Pick a month and a year to see your dates.

  • Every 3 months Quarterly test Water moving through the system proved to raise the alarm
  • Every 6 months Half-yearly service The interim contractor service
  • Every 12 months Annual service The full service, with the pump proved under flow
  • BS EN 12845

Counted from the visit you picked. If that was not the annual service, the annual may fall sooner. Your insurer or fire strategy can ask for more.

Book the visit or ring 07927 555475

Tell us the building. We will tell you what it is due.

No survey fee to find out where you stand. Describe the site and we will tell you which intervals apply and what the visit involves.

Based
37 Dickens Drive, Kettering, NN16 9EG
Covering
Kettering · Corby · Wellingborough · Northampton · Rushden · Daventry · Market Harborough · Bedford and England, from our base in Kettering
Office hours
Monday to Friday, 7am to 5pm. Emergency line any hour.

What do you need?
Type of building optional
Who do we come back to?

    If it is urgent, ring rather than write. We are on the phone Monday to Friday, 7am to 5pm, and outside those hours the same number reaches the emergency line.

    Or send it straight to us

    Or just ring 07927 555475 and talk it through. Mon to Fri, 7am to 5pm. Emergencies any hour.